4RD5 |
Field of Application:
- Fixed Compensation Units 4RD5 are used for fixed compensation in power systems
- With a converter load under 20% of the total load.
Principle:
- Eco-friendly, dry MKK technology (metalized plastic film, compact design), mounted in sheet-steel or moulded-plastic housings
- Connecting cable
- Supplied in sheet-steel or moulded-plastic houses
- Terminal stripes type 8WA are provided up to 25 kvar
- Stud terminals are provided for units over 25 kvar
Characteristics:
- 5 to 100 kvar per housing, PCB-free, impregnated with nitrogen
- Supplied for system voltages used throughout the world
- Reliability due to internal cut-off protection, high switching capability, self-healing and low dissipation
- High current carrying capacity, up to 1.3 times rated current as reserve for system voltage variations and any harmonic content that is present
- Ready for connection, with discharge device, type also with LV HRC switch-disconnector
________________________________________________________________________
 |
4RY |
Field of Application:
- For centralized power factor correction of inductive loads in power systems
- without or with a converter load under 20% of the total load
Principle:
- The power factor controller measures the reactive power present and, when deviations from the setpoint occur, it issues switching commands to contactors. These switch capacitor branches in or out depending on the requirements.
- For small power factor correction units the controller MODL CC is used.
Characteristics:
- Save energy costs, relieve connecting cables by the application of compact, reliable 4RY small power factor correction units
- Easy insatallation, small space requirements, ready for connection
Type-tested switchgear assembly (TSK) according to EN 60439-1, IEC 439-1 for indoor installation
- Comprehensive range of types, various housing variants or base plates for use in customer`s at hand housings
_________________________________________________________________________
 |
4RY18 |
Field of Application:
- Used in low-voltage power systems with low harmonic content, corresponding to a proportion of non-linear load under 20% of the upstream transformer rated power supplied for almost all system voltages occurring throughout the world
- Ratings from 75 to 500 kvar per unit, where required also with upstream AF blocking device
Principles:
- The power factor controller measures the inductive reactive power present in the network and also the corresponding power factor. It compares this with the set target cos phi and switches capacitors in or out as required using the contactors in the capacitor modules
- The number of switchings is optimized
Characteristics:
- Saving energy costs, relieving transformers and connecting cables, reducing transmission losses by the application of 4RY power factor correction units
- Controlled centralized compensation, ready for connection for main and subdistribution in power systems with non-linear loads under 20% of the upstream transformer rated power
- Type-tested switchgear assembly (TSK) according to EN 60439-1, IEC 439-1 for indoor insatallation
- Comprehensive range of types, various housing variants, natural cabinet cooling, degrees of protection up to IP54
______________________________________________________________________
 |
4RY57 |
Field of Application:
- For forming power factor correction units without reactors
- Suitable for use in low-voltage networks with a low harmonic content, corresponding to a proportion of non-linear load under 20% of the upstream transformer rated power
- Ratings from 25 to 200 kvar per unit
- Supplied for almost all system voltages occurring throughout the world
Principles:
- The 4RY57 modules with LV HRC fuse switch-disconnectors on a galvanized sheetsteel chassis are fitted with dry-type 4RB5 MKK power capacitors with capacitor contactors and with discharge devices
- Each modul has a 60 mm busbar adapter system with copper bars E-Cu 30 x 10 mm mounted at the front
Characteristics:
- Type-tested switchgear assembly (TSK) according to EN 60439-1, IEC 439-1 for forming power factor correction units
- Comprehensive range of types for 600 mm and 800 mm cabinet width, cabinet depth of 400 mm is sufficient
- With 8US1 front busbar adapter system, copper bars E-Cu 30 x 10 mm LV HRC fuse switch-disconnectors and with control line plug supplied for system voltages used throughout the world
_________________________________________________________________________